型号 | 风量(CMH) | 静压(Pa) | 电压(V) | 频率(Hz) | 功率(W) | 焓交换效率(%) | 温度交换效率(%) | 噪音(dB) | 重量(Kg) |
制冷 | 制热 |
QFA-D150S | 150 | 195 | 220 | 50 | 87 | 51 | 60 | 69 | 38 | 33 |
QFA-D250S | 250 | 220 | 220 | 50 | 145 | 51 | 59 | 70 | 40 | 33 |
QFA-D350S | 350 | 285 | 220 | 50 | 255 | 60 | 68 | 68 | 42 | 45 |
QFA-D500S | 500 | 295 | 220 | 50 | 265 | 53 | 61 | 65 | 43 | 45 |
QFA-D800S | 800 | 380 | 220 | 50 | 446 | 52 | 59 | 62 | 45 | 74 |
QFA-D1000S | 1000 | 395 | 220 | 50 | 530 | 53 | 61 | 65 | 48 | 84 |
QFA-D1500S | 1500 | 485 | 220 | 50 | 1165 | 54 | 66 | 68 | 50 | 80 |
QFA-D2000S | 2000 | 510 | 220 | 50 | 1420 | 55 | 67 | 66 | 52 | 90 |
QFA-D2500S | 2500 | 220 | 380 | 50 | 900 | 66 | 69 | 75 | 59 | 145 |
QFA-D3000S | 3000 | 210 | 380 | 50 | 1100 | 65 | 68 | 75 | 60 | 145 |
QFA-D4000R | 4000 | 260 | 380 | 50 | 1800 | 66 | 69 | 75 | 63 | 230 |
QFA-D5000R | 5000 | 280 | 380 | 50 | 2360 | 65 | 68 | 75 | 63 | 290 |
QFA-D6000R | 6000 | 300 | 380 | 50 | 3600 | 66 | 69 | 76 | 66 | 340 |
QFA-D8000R | 8000 | 300 | 380 | 50 | 6000 | 65 | 69 | 76 | 68 | 530 |
QFA-D系列吊装式静音小型机:风量150m3/h-2000m3/h,采用静音设计,适用于办公室、会议室、计算机房、住宅、宾馆客房、医院病房等小型场所;风量350m3/h-3000m3/h一般都有现货,发货时间大概在3天左右,
3000风量以上的机型属于工厂订做机型,需要先付定金后安排生产,交货时间需下单后再确定!

全热交换器原理:通常是指一种含有全热交换芯体的新风、排风换气设备。其工作原理是:产品工作时,室内排风和新风分别呈正交叉方式流经换热器芯体时,由于气流分隔板两侧气流存在着温差和蒸汽分压差,两股气流通过分隔板时呈现传热传质现象,引起全热交换过程。夏季运行时,新风从空调排风获得冷量,使温度降低,同时被空调风干燥,使新风含湿量降低;冬季运行时,新风从空调室排风获得热量,温度升高,同时被空调室排风加湿。这样,通过换热芯体的全热换热过程,让新风从空调排风中回收能量。


产品安装方法:



选型指南
1、根据建筑物结构特点选择不同安装形式的新风系统。 2、根据房间用途、面积、内部人员数量确定合适的新风量。 3、根据确定的新风量选择设备的规格和数量。 民用舒适性空调房间所需新风量 
|
确定房间所需新风量时,应根据房间空间大小及室内人员数量综合考虑。根据上表推荐数据分别按“每人所需新风量”和“房间新风换气次数”计算出新风量数值,取二者中较大值,作为设备选型依据。
对于特殊行业,如医院(手术室、特护病房)、实验室、工业车间、按该行业相关设计规范确定所需新风量。
计算示例:
某计算机房面积S=60(m2),净高h=3(m),人员n=10(人),若按每人所需新风量计算,取每人所需新风量q=70(m3/h),则新风量Q1=n·q=10×70=700(m3/h)。
若按房间新风换气次数计算,取房间新风换气次数p=5(次/h)。
则新风量Q2=p·s·h=5×60×3=900(m3/h)。
由于Q2>Q1,故取Q2(即900m3/h)作为设备选型参数数据。